Permit Number: T06CM06268
Parcel: 13824164B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM06268
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/11/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
12/13/2006 TERRY STEVENS ZONING REVIEW Approved
12/13/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the ventilation for the barber shop meets the minimum ventilation requirements of Section 403.3, IMC 2003.
2. Draw the floor plans to scale.
12/13/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM06268 12/13/06

1. Provide a panel and circuit number for all new electrical loads.
2. Perform feeder and service load calculations.
12/13/2006 ROBERT SHERRY WATER REVIEW Approved
12/13/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) CLARIFY CODE ANALYSIS ALLOWABLE SQ. FOOTAGE OF BUILDING AND ACTUAL SQ. FOOTAGE OF BUILDING.
2) FPRE SEPARATED USE CLARIFY FIRE SEPARATION WALL RATING, LOCATION, AND ADJACENT TENANTS.
3) PROVIDE COST OF CONSTRUCTION. RESTROOM IS NOT FULLY ACCESSIBLE. JUSTIFY PER IBC 2003 SECTION3409.6 20% COST OF CONSTRUCTION BEING SPENT TOWARDS ACCESSIBLITY. PROVIDE BUDGET BREAKDOWN ON DRAWINGS FOR JUSTIFICATION.
12/13/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/27/2006 FSANCHE1 WWM REVIEW Needs Review
12/27/2006 FSANCHE1 FIRE REVIEW Needs Review
12/27/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review