Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM06268
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/11/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 12/13/2006 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 12/13/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that the ventilation for the barber shop meets the minimum ventilation requirements of Section 403.3, IMC 2003. 2. Draw the floor plans to scale. |
| 12/13/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM06268 12/13/06 1. Provide a panel and circuit number for all new electrical loads. 2. Perform feeder and service load calculations. |
| 12/13/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/13/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) CLARIFY CODE ANALYSIS ALLOWABLE SQ. FOOTAGE OF BUILDING AND ACTUAL SQ. FOOTAGE OF BUILDING. 2) FPRE SEPARATED USE CLARIFY FIRE SEPARATION WALL RATING, LOCATION, AND ADJACENT TENANTS. 3) PROVIDE COST OF CONSTRUCTION. RESTROOM IS NOT FULLY ACCESSIBLE. JUSTIFY PER IBC 2003 SECTION3409.6 20% COST OF CONSTRUCTION BEING SPENT TOWARDS ACCESSIBLITY. PROVIDE BUDGET BREAKDOWN ON DRAWINGS FOR JUSTIFICATION. |
| 12/13/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/27/2006 | FSANCHE1 | WWM | REVIEW | Needs Review | |
| 12/27/2006 | FSANCHE1 | FIRE | REVIEW | Needs Review | |
| 12/27/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |