Permit Number: T06CM06267
Parcel: 12009052A

Address:
4415 S 6TH AV

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T06CM06267
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved 1. ADD HANDRAILS ON EACH SIDE OF INTERIOR RAMP PER NOTE ON SHEET A-1 (REFER IBC SECTION 1010).
11/13/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/17/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The revised drawing does not reflect the field revisions to the waste piping (e.g. there is only one service sink, not two, and each fixture trap has a vent). Revise the waste piping plan and the waste and vent diagram. Reference: Section 103.2.3, UPC 2006.
11/18/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved All comments from lab review on 8/26/08 corrected,also items from RTM review 10/23/08 corrected,
RTM 11/08/08

Final Status

Task End Date Reviewer's Name Type of Review Description
11/21/2008 GERARDO BONILLA OUT TO CUSTOMER Completed
11/21/2008 SUE REEVES REJECT SHELF Completed