Permit Number: T06CM06267
Parcel: 12009052A

Address:
4415 S 6TH AV

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T06CM06267
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Overcurrent protective device for Water Heater illegible on panel schedule.
2. Plumbing plans call for a 20A Water Heater. Electrical looks like 12.5A, but this is also not quite legible. Please clarify, and correct load calculations as necessary.
3. Check overcurrent protective device sizing for Water Heater per NEC 422.11.
4. Provide documentation that Water Heater is cord-connected, or provide local disconnect.
5. PROVIDE COMPLETE SET OF PREVIOUSLY APPROVED PLANS.
02/21/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed No mechanical revisions shown.
02/21/2008 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied PREVIOUS DENIAL NOTES NOT ADDRESSED:

1) PROVIDE COMPLETE SET OF PREVIOUSLY APPROVED PLANS.

2) INDICATE ACCESSIBLE ROUTE FROM OFFICE/SALES AREA TO ACCESSIBLE RESTROOM.

3) THERE MAY BE OTHER CORRECTIONS REQUIRED. DSD CANNOT PERFORM A COMPLETE REVIEW WITHOUT ALL THE INFORMATION FROM PREVIOUSLY APPROVED PLANS AND ALL THE INFORMATION FOR MODIFIED ITEMS.
02/21/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a copy of the approved construction documents as a reference.
2. Indicate the extent of the revisions by clouding the revisions on a clean copy (i.e. not showing any previous City of Tucson or Pima County approval stamps) of the affected drawings. Redraw as required to clearly show the revised conditions. The current registrant shall clearly indicate the extent of the design for which he is taking responsibility.
3. PVC piping is not approved for use inside of a building. Reference Section 604.1, UPC 2003.
4. Clarify the water distribution. Why are two cold water lines are serving the drinking fountain and only one to the service sink?
5. Coordinate the plumbing and electrical plans with regard to the tankless water heater.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/26/2008 CPIERCE1 OUT TO CUSTOMER Completed
02/26/2008 SHANAE POWELL REJECT SHELF Completed