Permit Number: T06CM06265
Parcel: 136406740

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM06265
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The architectural details showing the wall connection requirements for the water heater installation (Detail 1/P3.0) do not appear to be adequate to support the specified water heater. The wall is an interior partition constructed of 25-gage metal studs and gypsum board with no internal blocking to accept the bolts and the holes in the 6"x6" plates are too small for the specified lag bolts. Resolve the physical incongruities and provide calculations to justify the methods of support. Reference Section 103.2.3, UPC 2003.
2. All storage-type water heaters located in a water system having a check valve or a backflow preventer must be provided with a means to control water expansion. Please show how this is to be accomplished. Reference Section 608.3, UPC 2003 with local amendments.
02/05/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 2/05/07
ACTIVITY NUMBER: T06CM06265
PROJECT NAME: SLEEP AMERICA
PROJECT ADDRESS: 9660 E. 22ND ST
ARCHITECT / ENGINEER: PHOENIX DESIGN ONE
PROJECT REVIEWER: CHRISTY FOREMAN


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CHRISTY.FOREMA1@TUCSONAZ.GOV IF YOU CARE TO DISCUSS.

1) Display Arch wall - please justify per section 1621.1.2 IBC 2003. Overall height is 7'-0" therefore provide lateral bracing or provide structural calculations justifying seismic load does not exceed 5 psf required in section 1607.13.
02/07/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/21/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
02/21/2007 SUE REEVES REJECT SHELF Completed