Permit Number: T06CM06265
Parcel: 136406740

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM06265
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Circuit A5-10 is designated on the Lighting Plan, but is listed as a spare on the panel schedule. Please clarify.
2. Please note that track lighting shall be counted at 75 VA/LF for feeder calculations. Reference NEC 220.12 (B). (36) (75) = 2700 VA on A5-8. Additional 25% if these fixtures are anticipated to operate continuously.
3. Account for continuous load and largest motor in panel/feeder calculations. If these have already been factored in, clarify such on the plans.
01/12/2007 GERRY KOZIOL WWM REVIEW Approved
12/14/2006 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/15/2006 DAVE MANN FIRE REVIEW Approved
12/18/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide the architectural details showing the wall connection requirements for the water heater installation (Note 6, Detail 1/P3.0). Reference Section 103.2.3, UPC 2003.
12/18/2006 ROBERT SHERRY WATER REVIEW Approved
12/18/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/22/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 12/22/06
ACTIVITY NUMBER: T06CM06265
PROJECT NAME: SLEEP AMERICA
PROJECT ADDRESS: 9660 E. 22ND ST
ARCHITECT / ENGINEER: PHOENIX DESIGN ONE
PROJECT REVIEWER: CHRISTY FOREMAN


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CHRISTY.FOREMA1@TUCSONAZ.GOV IF YOU CARE TO DISCUSS.

1) Minimum text size shall be 1/8" = 1'-0" on all drawings.
2) Display Arch wall - please justify per section 1621.1.2 IBC 2003.
3) Sales / service counter clarify location of millwork that complies with section 904.3 ANSI A117.1 2003.
4) Dimension north storage room wall.
5) Justify occupant load for retail space and storage space.