Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO
Permit Number - T06CM06239
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/19/2007 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T06CM06239 3/22/07 8222 E. DOMINIC ST. PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2003 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. SITE PLAN: 1. PLEASE SIZE THE WATER SERVICE LINE ON BOTH SIDES OF THE "T". FOUNDATION PLANS: 1. HOLD DOWN SCHEDULE, 2 ; SHOULD THE HOLD DOWN 2 BE A HPAHD22 INSTEAD OF HPAHD42 ? TYPO? FLOOR PLANS: 1. PLEASE ILLUSTRATE THE HAND RAIL LOCATIONS ON THE STAIRWAY. SEE R311.5.6 . 2. SHOW THAT EACH WATER CLOSET IS LOCATED IN A CLEAR SPACE NOT LESS THAN 30" WIDE AND HAS A CLEAR SPACE IN FRONT OF NOT LESS THAN 24" PER R307.2 (FIGURE). STRUCTURAL PLANS: 1. GRENIER ENGINEERING, SHEET 12, FLOOR DIAPHRAM: "1¼" T&G USED" vs DETAILS ON PLANS SHEET 7 USES ¾". PLEASE CO-ORDINATE. 2. PLANS, SHEET 3, HOLD DOWN 2; SHOULD IT BE "HPAHD22" vs "HPAHD42"? I CAN'T FIND A "HPAHD42" IN SIMPSON. THE "PAHD42" REQUIRES 8" END DISTANCE TO ACHIEVE 1800# AND CAN'T BE ON THE END STUD. IS THIS OKAY OR A TYPO? ELEVATIONS: 1. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL VENTS NEEDED TO COMPLY. SECTIONS - DETAILS - MISC. NOTES: 1. 1 / 4 ; ARE THE STRINGERS AND PLATE PRESSURE TREATED? SEE R319.1 ITEM 3 . 2. 6 / 7 ; PLEASE SPECIFY THE JOIST HANGERS. 3. 6 / 7 ; PLEASE SPECIFY THE LEDGER TO BEAM CONNECTION. ELECTRICAL PLANS: 1. PLEASE CHECK MATH IN LOAD CALCULATIONS. LIGHTING CODE: 1. PLEASE PROVIDE THE LIGHTING CODE CALCULATIONS AND FIXTURE CUT SHEET. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 791-5550 EXT. 1110 HEY, NICE PLAN !!! |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/27/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 03/27/2007 | GERARDO BONILLA | REJECT SHELF | Completed |