Permit Number: T06CM06232
Parcel: 10408077E

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T06CM06232
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Royal South Display Lot
T06CM06232
Site Plan (2nd Review)

TRANSMITTAL DATE: March 1, 2007

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for full code compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for the proposed expansion only. Provide a copy of the last approved site plan so that Zoning can verify the percent of expansion of floor area and vehicle use area. Once provided and verified additional comments may be forth coming.

2. This comment has not been fully addressed. Based on the last approved site plan there is a difference in the square footage of Building 'B'. The last approved plan shows 24,255 where as this site plan shows 27,120 which is a difference of 2,865 square feet, clarify. The building expansion calculation is incorrect. The prior expansion exceeded the 25% which required full code. This expansion would be the proposed building, 5,184 square feet, divided by the total of phase 1 & 2, 47,176, or a building expansion of 11%, revise the building expansion calculation. D.S. 2-02.2.2.5 Provide a calculation for the building and lot expansion.

3. The street name shown under "ADDRESS" of "DEVELOPMENT DATA" is incorrect. The street name is CIRCUIT ROAD, not DRIVE, revise.

4. Ensure that all changes to the site plan are reflected on the landscape & grading plan.

5. Zoning will provide an over the counter review once the above comments have been addressed. Call or email for an appointment.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 791-5608 ext. 1180.

C:\planning\site\t06cm06232.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
03/01/2007 STEVE SHIELDS ZONING HC SITE REVIEW Approved
03/12/2007 ANDREW CONNOR NPPO REVIEW Approved
03/12/2007 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Provide correct calculations for the building and lot expansion. (See Zoning comments regarding expansion calculations).

2. Within a vehicular use area, one (1) canopy tree is required for each 10 motor vehicle parking spaces and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1. Canopy tree definition is as follows: A woody plant, other than a palm tree, with a mature crown diameter of at least fifteen (15) feet and having a trunk that, at maturity, is kept clear of leaves and branches at least six (6) feet above grade. Palm trees cannot be used for canopy requirement for vehicle use area. Clarify areas used for display or vehicle use on the site and landscape plans.

3. The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. Ensure that all changes to the site plan are reflected on the landscape & grading plan.
03/19/2007 SUZANNE BOHNET ENGINEERING REVIEW Denied DATE: March 21, 2007
FROM: Suzanne Bohnet, CFM
Engineering Division

SUBJECT: 4670 N. Circuit Rd.
Land Rover/Jaguar Dealership
Site Plan T06CM06232 (Second Review)

RESUBMITTAL REQUIRED: Site Plan and Grading Plan.

The Site Plan and Grading Plan cannot be approved as submitted.

Site Plan:
1. From previous comments, for legibility and reproduction, ensure that all type is a minimum 12-point size and easily read (not overlaid by shading or other words). Specifically, Sheet CO contains type that is not 12-point size.

Grading Plan:
2. 1. From previous comments, for legibility and reproduction, ensure that all type is a minimum 12-point size and easily read (not overlaid by shading or other words). Specifically, Sheet C2 contains type that is not 12-point size.

Per Zoning and Landscape's comments ensure that all changes on the Site Plan are reflected on the Grading Plan and Landscape Plan.

Engineering will provide an over-the-counter review once the above comments have been addressed. Call or email for an appointment. Provide 4 copies of the Grading Plan and 3 copies of the Stormwater Pollution Plan for this review.

Please do not hesitate to contact me with any questions.

Thank you,
Suzanne Bohnet, CFM
Engineering Associate
(520) 791-5550 x1188 office
Suzanne.Bohnet@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
03/22/2007 FSANCHE1 OUT TO CUSTOMER Completed
03/22/2007 FSANCHE1 REJECT SHELF Completed