Permit Number: T06CM06231
Parcel: 110055590

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM06231
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/08/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
12/08/2006 ANY ENGINEERING REVIEW Approved
12/08/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM06231 12/8/06

1. Provide an electrical circuit for EF-1. Reference Sheet M1.1.
2. Distinguish new from existing loads on panel schedule.
3. Show HP-1 on electrical plans.
4. Provide an electrical circuit for HP-2. Reference Sheet M0.1.
5. Adjust load calculations per the above comments.
12/08/2006 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
12/11/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/11/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/11/2006 ROBERT SHERRY WATER REVIEW Approved
12/11/2006 DAVE MANN FIRE REVIEW Approved
12/11/2006 RSHERRY1 WWM REVIEW Passed
12/12/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review