Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM06206
Parcel: 13313005F

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T06CM06206
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/14/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM06206 5/11/07

1. "NEW PUMP PANEL P" is shown twice on the plans.
2. Put a plaque on the new panel which reads: "This panel powers only exterior loads."
3. Service load calculations shall meet the requirements of NEC Article 220. No reference to 15VA/SF in such article.
4. For series ratings we require that line side and load side overcurrent protective devices be specified. The ratings as described in the subject project imply a three-tiered system, not available commercially. In any case, it appears that the available fault current is less than 10,000A at the new panel. If you provide the fault calculations to demonstrate this, you could same your client considerable expense.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/16/2007 THAUSER1 OUT TO CUSTOMER Completed