Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2006 STEVE SHIELDS ZONING REVIEW Approved
12/06/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
12/06/2006 SSHIELD1 NPPO REVIEW Passed
12/07/2006 DAVE WITT BUILDING-RESIDENTIAL REVIEW Approved
12/08/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM06205 12/7/06

1. Two sets of all documentation necessary for over-the-counter service.
2. Indicate the location of the service panel and the inverter on the plans.
3. Since the intent is to install the inverter inside of the building, specify the conduit type as being metallic. Note that this is also on the model plans.
4. Since the intent is to install the inverter inside of the building, provide the plaques required by NEC 690.56 (B).
5. Provide the rating of the service panel and the rating of the overcurrent protective device protecting the main of that panel. Reference NEC 690.64 (B) (2).