Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/06/2006 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
12/06/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
12/06/2006 | SSHIELD1 | NPPO | REVIEW | Passed | |
12/07/2006 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Approved | |
12/08/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM06205 12/7/06 1. Two sets of all documentation necessary for over-the-counter service. 2. Indicate the location of the service panel and the inverter on the plans. 3. Since the intent is to install the inverter inside of the building, specify the conduit type as being metallic. Note that this is also on the model plans. 4. Since the intent is to install the inverter inside of the building, provide the plaques required by NEC 690.56 (B). 5. Provide the rating of the service panel and the rating of the overcurrent protective device protecting the main of that panel. Reference NEC 690.64 (B) (2). |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/08/2006 | DELMA ROBEY | APPROVAL SHELF | Completed |
12/08/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
12/08/2006 | DELMA ROBEY | REJECT SHELF | Completed |