01/11/2007 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity # T06CM06198

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

As of 9-02-04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the 2003 UPC with amendments. All plans should reference these codes. See this site for all adopted amendments: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html


FOUNDATION PLANS:

1. Clarify the footing dimensions. Detail 3/S1.1 is referenced at the F2 location, but inconsistent dimensions are provided.
2. Revise the anchor-bolt dimension. Detail 4/S1.1 shows the anchor-bolt with 5" concrete embedment, but R403.1.6 requires 7" embedment into concrete.

STRUCTURAL PLANS:

1. Complete the post base installation requirement. Detail 4/S1.1 shows a Simpson post base, but does not note the recommended epoxy connection needed for uplift capacity.
2. Size the post, and completely detail and all connections to the foundation and/or wall framing members for the B1 beam supports. Detail 6/S1.1 notes a post, but Key Note #7 notes a trimmer assembly. Also, verify the required footing.

SECTIONS - DETAILS - MISC. NOTES:

1. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c framing, IRC table R702.3.5 footnote d. The GWB is noted at note #3 and detail 7 & 8/S1.1.


If you have any questions, please contact your assigned plans examiner Ken Van Karsen at 791-5550, extension 1112.