Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM06193
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/06/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
12/06/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
12/06/2006 | JWILLIA5 | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
12/06/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/06/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/06/2006 | RSHERRY1 | WWM | REVIEW | Passed | |
12/06/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
12/06/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
12/07/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
12/07/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |