Permit Number: T06CM06153
Parcel: 140020040

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T06CM06153
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2007 DAVE MANN FIRE REVIEW Approved
01/17/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Verify that the water service connection to each building has an accessible full-way shut off valve. Reference Section 605.2, UPC 2003.
2. Provide building shut off valves for the electric shop and the engineering building that comply with Section 605.2, UPC 2003, i.e. the water service to each building shall be able to be shut off without affecting any other building.
3. Show how the new domestic water distribution system is to comply with Section 608.2, UPC 2003.
4. Provide a low-pressure cut off switch prior to the domestic water booster pump system. Reference Section 609.8, UPC 2003.
01/17/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
01/17/2007 RSHERRY1 WWM REVIEW Passed
01/17/2007 ROBERT SHERRY WATER REVIEW Denied A reduced pressure backflow prevention assembly is required to be installed as close as practical to the Tucson Water service connection (i.e. the meter) to separate the public water supply from the private water piping. The booster pump arrangement shown on sheet 03140-P8 does not appear to provide protection for the public water supply. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
01/22/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/02/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
02/05/2007 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed impact fees do apply, no site/development plan submitted by deadline
eastern district
616 sf
$678.01
03/07/2007 SUZANNE BOHNET ENGINEERING REVIEW Approved Electrical lines / utility improvements.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/11/2007 VFLORES1 OUT TO CUSTOMER Completed