Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/08/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
01/17/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Verify that the water service connection to each building has an accessible full-way shut off valve. Reference Section 605.2, UPC 2003. 2. Provide building shut off valves for the electric shop and the engineering building that comply with Section 605.2, UPC 2003, i.e. the water service to each building shall be able to be shut off without affecting any other building. 3. Show how the new domestic water distribution system is to comply with Section 608.2, UPC 2003. 4. Provide a low-pressure cut off switch prior to the domestic water booster pump system. Reference Section 609.8, UPC 2003. |
01/17/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
01/17/2007 | RSHERRY1 | WWM | REVIEW | Passed | |
01/17/2007 | ROBERT SHERRY | WATER | REVIEW | Denied | A reduced pressure backflow prevention assembly is required to be installed as close as practical to the Tucson Water service connection (i.e. the meter) to separate the public water supply from the private water piping. The booster pump arrangement shown on sheet 03140-P8 does not appear to provide protection for the public water supply. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf |
01/22/2007 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/02/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/05/2007 | BETSY COTTLE | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | impact fees do apply, no site/development plan submitted by deadline eastern district 616 sf $678.01 |
03/07/2007 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | Electrical lines / utility improvements. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/11/2007 | VFLORES1 | OUT TO CUSTOMER | Completed |