Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Permit Number - T06CM06146
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/04/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 12/04/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 12/04/2006 | HEATHER THRALL | NPPO | REVIEW | Passed | |
| 12/04/2006 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Approved | |
| 12/05/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM06146 12/4/06 1. Indicate the rating of the overcurrent protective device on the sub-panel at the garage. Reference NEC 690.64 (B) (2). 2. Provide written permission from Steven J. Metzger allowing an annotation of the model plans changing the wording on the Interconnection Diagram from "Customer Main AC Service Panel" to read "Electrical Sub-Panel." 3. Specify the plaque required by NEC 690.56 (B), to be installed at the Main Service Disconnect, the Photovoltaic Disconnect at the Inverter, and the disconnecting means for the Sub Panel in the garage. Provide the exact wording. |