Permit Number: T06CM06146
Parcel: 125041810

Address:
2403 E 2ND ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T06CM06146
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2006 HEATHER THRALL ZONING REVIEW Approved
12/04/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
12/04/2006 HEATHER THRALL NPPO REVIEW Passed
12/04/2006 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Approved
12/05/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM06146 12/4/06

1. Indicate the rating of the overcurrent protective device on the sub-panel at the garage. Reference NEC 690.64 (B) (2).
2. Provide written permission from Steven J. Metzger allowing an annotation of the model plans changing the wording on the Interconnection Diagram from "Customer Main AC Service Panel" to read "Electrical Sub-Panel."
3. Specify the plaque required by NEC 690.56 (B), to be installed at the Main Service Disconnect, the Photovoltaic Disconnect at the Inverter, and the disconnecting means for the Sub Panel in the garage. Provide the exact wording.