Permit Number: T06CM06145
Parcel: 129022180

Address:
2825 E DEVON ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM06145
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2007 DANIEL RUSCH BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity # T06CM06145 #2



Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.


GENERAL REQUIREMENTS:

All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

FOUNDATION PLANS:

1. Show or note a 1" minimum separation of untreated exterior posts above the floor R319.1.4

FLOOR PLANS:

1. Interior braced panels require sill to foundation connections with ½" anchor bolts described in R403.1.6 & R602.10.8 Also indicate method of connecting brace panel to exterior wall.R602.10.8

SECTIONS - DETAILS - MISC. NOTES:

1. Roof, as shown, won't vent without any cross-flow provided by venting @ top of ceiling/room

ELECTRICAL PLANS:

1 Circuit 2/4 in panel A should be sized in #3 wire. E3605.1
2 Circuit for jacuzzi tub needs gfci protection.

If you have any questions, please contact your assigned plans examiner Daniel
Rusch at 791-5550, extension 1113

Final Status

Task End Date Reviewer's Name Type of Review Description
02/01/2007 DELMA ROBEY APPROVAL SHELF Completed
02/01/2007 DELMA ROBEY OUT TO CUSTOMER Completed
02/01/2007 GERARDO BONILLA REJECT SHELF Completed