02/26/2007 ROBERT SHERRY WATER REVIEW Denied Second request. Provide a letter from Tucson Water confirming that the use of a 1" water meter with a demand of 41.4 GPM will be allowed for this project.
02/27/2007 DAVE MANN FIRE REVIEW Approved Please add the following automatic sprinkler criteria to the plans:

1. The hazard classification of the occupancy including any special hazards.
2. The design standard to be used.
3. The availability and adequacy of the water supply.
4. The design density and the area of operation.
03/02/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: March 3, 2007
ACTIVITY NUMBER: T06CM06131
PROJECT NAME: Cope Behavioral Building Review
PROJECT ADDRESS: 2435 North Castro
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate



RE SUBMITTAL REQUIRED: BUILDING PLAN SET

SUBMITTAL REQUIRED: APPROVED SITE PLAN

1. The following review comment is based on a building plan review. It is acknowledged the site plan that was approved by the Fire and Engineering review sections was submitted. However the approved site plan must be stamped approved by Fire, Zoning and Engineering sections. Currently Zoning has not approved the site plan. Once Zoning approves the site plan, that site plan must be resigned by Fire and Engineering. Once this process is complete the building plan can be approved by the Zoning and Engineering review sections. This process can be completed over the counter. Please contact Patricia Gilbert to set up a time, 791-5550 ext. 2206.
03/08/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: COPE - Behavioral Services Incorporated
2435 N Castro Ave.
T06CM06131
Building Plan (2nd Review)

TRANSMITTAL DATE: March 8, 2007

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan at this time.

2. The submitted site plan states "FRONTAGE YARD = WALL HGT 'H' = 16'-8" x 1.5 = 25'-0" REQUIRED. Based on the provided East Elevation the building, the height of the building wall is 17'-6", this wall height requires a 26'-4" setback. The building height is measured from design grade to top of parapet.

3. Zoning acknowledges that the site plan has been approved by Zoning, Engineering and Fire. The site plan has been stamped by Zoning and requires re-stamps from Engineering and Fire. Once this process is complete in the above setback issue is resolved the building plan can be approved by the Zoning and Engineering review sections.

4. This process can be completed over the counter. Phone or email to setup an appointment for this over the counter review.


If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 791-5608 ext. 1180.

C:\planning\building\t06cm06131-2nd.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved and stamped site plan and additional requested documents