Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T06CM06126
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/07/2006 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T06CM06126 12/22/06 6042 S. EUCLID PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2003 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FOUNDATION PLAN: 1. PLEASE DIMENSION THE LOCATION OF THE INTERIOR FOOTINGS. FLOOR PLANS: 1. HOW DOES THE EXISTING READING ROOM GET FRESH AIR? SEE R303.1 . SEE ALSO THE EXCEPTIONS. 2. PLEASE SEE R602.10 RE: BRACED WALL PANELS. GYPSUM BOARD BWPs REQUIRE 8 LINEAL FEET. SEE ALSO R602.10.6 RE: HOLD-DOWNS FOR ALTERNATE BWPs. 3. HOLD DOWN SCHEDULE / A-2 ; PLEASE CHECK THE DESCRIPTION OF THE "HPAHD -42". DID YOU MEAN "HPAHD-22"? THE "PAHD-42" DOESN'T ACHIEVE THE REQUIRED 1800# OF TENSILE STRENGTH UNTIL IT'S 8" FROM THE CORNER AND WON'T BE ON THE LAST STUD. 4. FIREPLACE: - INDICATE FIREPLACE LOCATION, HEARTH SIZE AND MATERIALS, PER R1003.10 OR R1004.2 - FOR FACTORY BUILT OR ZERO CLEARANCE FIREPLACES, PROVIDE CUT SHEETS, MAKE, MODEL NUMBER AND THE APPROVAL NUMBER OF THE APPROVED TESTING AGENCY (IE: ICBO #), PER R1002 ALL SHALL COMPLY WITH UL127. - FOR MASONRY FIREPLACES, SHOW CROSS-SECTION, PER R100. PLEASE IGNORE THIS IF THE TOP LEFT CORNER OF THE FAMILY ROOM HAS A PLATFORM WITH NO FIREPLACE ELEVATIONS: 1. EAST, WEST ELEVATIONS / A-5 ; PLEASE SPECIFY SIZES OF THE GABLE VENTS. SECTIONS - DETAILS - MISC. NOTES: 1. SHEAR WALL SCHEDULE / A-2 ; PLEASE SPECIFY THE MINIMUM LENGTHS OF SW-1 AND SW-2. SEE R602.10 2. 2 / A-3 ; PLEASE MENTION THE LATH AND WEEP SCREED. 3. 1 / A-4, FRAMING PLAN ; PLEASE ILLUSTRATE THE CRICKETS ON THE EXISTING AND NEW ROOFS. 4. 2, 12 / A-4, NOTE 12 ; PLEASE SPECIFY "SAG-RESISTANT" FOR ½" GYP BOARD ON CEILINGS FRAMED AT 24" O.C. SEE TABLE R702.3.5 , FOOTNOTE "d". 5. 3 / A-4 ; PLEASE SPECIFY THE TRUSS / PLATE CONNECTION. 6. 3 / A-4 ; IS THE 5/8" GYP BOARD ON THE CEILING AN OPTION TO THE ½" MENTIONED IN 2 / A-4? 7. 4 / A-4 ; PLEASE PROVIDE A NAILER FOR THE 5/8" GYP BOARD ON THE CEILING. 8. 4 / A-4 ; PLEASE PROVIDE VENTILATION FOR THE CRICKET AND UNDER LYING ROOF. 9. 2, 4 / A-4 ; PLEASE PROVIDE A PLATE OR SOME OTHER METHOD TO NEGATE THE POINT LOAD OF THE RAFTERS ON THE OVER FRAMED ROOF SHEATHING. 10. 6 / A-4 ; PLEASE INSULATE THE STUDS UP TO THE ROOF DECK'S INSULATION. ELECTRICAL PLANS: 1. A RECEPTACLE IS REQUIRED FOR THE FRONT AND BACK YARD USE. PLEASE SEE E3801.7 . 2. THE RECEPTACLE IN THE BATH ROOM ISN'T PERMITTED TO BE ON CIRCUIT 24. SEE E3603.4. MANY PEOPLE DON'T READ THE EXCEPTION WHICH MIGHT BE OF USE. 3. GENERAL ELECTRIC NOTE 8 / E-1 ; DOES THE "40 WATT MINIMUM" CONFLICT WITH THE LIGHTING CODE? DID YOU MEAN "MAXIMUM"? ALSO, PROVIDE FIXTURE A OR REFER TO 3 / E-1. THE LIGHTING ZONE SHOULD BE "E-3" INSTEAD OF "E-3a". 4. ELECTRIC LOAD CALCULATION / E-1 ; THE FIRST 10KW SHOULD BE AT 100% INSTEAD OF THE FIRST 8KW. PLEASE SEE TABLE E3508.2 . IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 791-5550 EXT. 1110 |
| 12/08/2006 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/03/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 01/03/2007 | SUE REEVES | REJECT SHELF | Completed |