Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM06124
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/05/2006 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 12/05/2006 | JOHN WILLIAMS | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 12/06/2006 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 12/06/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM06124 12/6/06 THIS IS AN INCOMPLETE REVIEW. OUT OF SCOPE FOR OVER THE COUNTER. 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Indicate load on panel schedule for Ckt LI-16,18, new CU. 3. Show Panel Schedule LH on plans. 4. It appears that the use of demand factor for Panel LB exceeds that allowed by NEC 220.13, in that certain receptacle loads involved exceed 180VA per outlet. Did not have time to check the other receptacle panels. 5. Provide fault current rating of New Panel LI. |
| 12/06/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 12/06/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/06/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |