Permit Number: T06CM06124
Parcel: 14041075A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM06124
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2006 DAVID RIVERA ZONING REVIEW Approved
12/05/2006 JOHN WILLIAMS BUILDING-COMMERCIAL REVIEW Needs Review
12/06/2006 DROBEY1 WWM REVIEW Needs Review
12/06/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM06124 12/6/06
THIS IS AN INCOMPLETE REVIEW. OUT OF SCOPE FOR OVER THE COUNTER.

1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Indicate load on panel schedule for Ckt LI-16,18, new CU.
3. Show Panel Schedule LH on plans.
4. It appears that the use of demand factor for Panel LB exceeds that allowed by NEC 220.13, in that certain receptacle loads involved exceed 180VA per outlet. Did not have time to check the other receptacle panels.
5. Provide fault current rating of New Panel LI.
12/06/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/06/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/06/2006 DELMA ROBEY OUT TO CUSTOMER Completed