Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM06118
Parcel: 129041830

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM06118
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2006 ANDREW CONNOR ZONING REVIEW Approv-Cond zoning inspection required to ensure parking lot re-striping per 1977 site plan.
11/30/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/30/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM06118 11/30/06

1. Enter electrical load on panel schedule for Ckt 16B.
2. Enter electrical load on panel schedule for Ckt 15B.
3. Electrical load on Ckt 13B appears to be 2700VA, not 900.
4. Electrical load on Ckt 13B appears to be 22.5A, which would overload a 20A Ckt.
5. If AC-1 load totals 77.5A, the VA would be 9300VA per phase, not 6210. Note that a 77.5A load would not be carried on a 50A Ckt.
6. Panel AC-2 load of 27A would not be protected by a 90A Breaker.
7. Load on Ckt B-20 appears to be 331VA, not 256.
8. Load on Ckt B-22 appears to be 556VA, not 492.
Rework all feeder load calculations.
11/30/2006 ROBERT SHERRY WATER REVIEW Approved
11/30/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
11/30/2006 RSHERRY1 WWM REVIEW Approved
11/30/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/30/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
11/30/2006 DAVE MANN FIRE REVIEW Approved
12/01/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed