Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM06101
Parcel: 14042002A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM06101
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2006 MARTIN BROWN FIRE REVIEW Approved
11/30/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Utility spaces are required to be ventilated per Section 403.3, IMC 2003.
2. Provide cooling load calculations for the storage and tele data rooms that justifies the use of a 5-ton air conditioner. Reference Section 803.2.1.1, IECC 2003.
11/30/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/30/2006 ROBERT SHERRY WATER REVIEW Approved
11/30/2006 RSHERRY1 WWM REVIEW Passed
12/26/2006 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
12/26/2006 DROBEY1 ENGINEERING REVIEW Needs Review
12/26/2006 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
12/26/2006 DROBEY1 ZONING REVIEW Needs Review
12/26/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/26/2006 DELMA ROBEY APPROVAL SHELF Completed
12/26/2006 DELMA ROBEY OUT TO CUSTOMER Completed
12/26/2006 DELMA ROBEY REJECT SHELF Completed