Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/30/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
11/30/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Utility spaces are required to be ventilated per Section 403.3, IMC 2003. 2. Provide cooling load calculations for the storage and tele data rooms that justifies the use of a 5-ton air conditioner. Reference Section 803.2.1.1, IECC 2003. |
11/30/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
11/30/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/30/2006 | RSHERRY1 | WWM | REVIEW | Passed | |
12/26/2006 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
12/26/2006 | DROBEY1 | ENGINEERING | REVIEW | Needs Review | |
12/26/2006 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
12/26/2006 | DROBEY1 | ZONING | REVIEW | Needs Review | |
12/26/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |