Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM06097
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/29/2006 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
11/29/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
11/29/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/29/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
11/30/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
11/30/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003. 2. Note 6, sheet D-1 calls for the water supplies to the demolished sink and lavatoryare to be capped off in the wall. Sheet A-1 does not reconnect the water supplies; clarify. |
11/30/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/01/2006 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE CORRECT CODE ANALYSIS. CLARIFY TOTAL BUILDING SQUARE FOOTAGE FOR NON SEPERATED USE. 2) CLARIFY HOW 20% COST OF CONSTRUCTION IS BEING SPENT TOWARD ACCESSIBILITY PER IBC 3409.6. IT APPEARS CORE RESTROOMS ARE NOT FULLY ACCESSIBLE; CODE REQUIRES FULLY ACCESSIBLE MEN'S AND WOMEN'S FACILITIES. |
12/01/2006 | FSANCHE1 | WWM | REVIEW | Needs Review | |
12/01/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/01/2006 | FSANCHE1 | OUT TO CUSTOMER | Completed |