Permit Number: T06CM06097
Parcel: 10821328B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM06097
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2006 STEVE SHIELDS ZONING REVIEW Approved
11/29/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
11/29/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
11/29/2006 MARTIN BROWN FIRE REVIEW Approved
11/30/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/30/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
2. Note 6, sheet D-1 calls for the water supplies to the demolished sink and lavatoryare to be capped off in the wall. Sheet A-1 does not reconnect the water supplies; clarify.
11/30/2006 ROBERT SHERRY WATER REVIEW Approved
12/01/2006 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE CORRECT CODE ANALYSIS. CLARIFY TOTAL BUILDING SQUARE FOOTAGE FOR NON SEPERATED USE.
2) CLARIFY HOW 20% COST OF CONSTRUCTION IS BEING SPENT TOWARD ACCESSIBILITY PER IBC 3409.6. IT APPEARS CORE RESTROOMS ARE NOT FULLY ACCESSIBLE; CODE REQUIRES FULLY ACCESSIBLE MEN'S AND WOMEN'S FACILITIES.
12/01/2006 FSANCHE1 WWM REVIEW Needs Review
12/01/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/01/2006 FSANCHE1 OUT TO CUSTOMER Completed