Permit Number: T06CM06092
Parcel: 12504083C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM06092
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2006 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE CODE ANALYSIS DATA SHEET FOR BUILDING AND T.I.
2) PROVIDE STRUCTURAL DETAILS FOR WALL FRAMING, CABINET BACKING, ETC.
3) INDICATE WALL FINISH OF HARD, NON-ABSORBANT SURFACE PER SECTION 1210.2 OF IBC.
4) CLARIFY HOW 2'10" DOOR TO ACESSIBLE RESTROOM WILL MEET ICC/ANSI A117.1 SECTION 404.2.2 .
5) TYPICAL USE OF NEW JERSEY REHABILITATION CODE IS FOR RENNOVATION OF AN EXISTING OCCUPANCY WITHOUT CHANGE OF USE. PLEASE PROVIDE PREVIOUS CofO SHOWING A-2 OCCUPANCY OR OTHER WAY TO JUSTIFY SINGLE UNISEX. CURRENT CODE REQUIRES 2 RESTROOMS IF OCC LOAD IS MORE THAN 15.
12/05/2006 ROBERT SHERRY WATER REVIEW Approved
12/05/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the plumbing drawings to include the changes shown on the 8-1/2"x 11" sheets.
2. The minimum font size is 1/8", all upper case.
3. Provide upper terminal clean outs for the lavatory and the hand sink. Reference Section 707.4, UPC 2003.
4. The provided water calculations indicate that the minimum water service pipe should be 1", not 3/4" as shown on sheet P-1. Coordinate the water pipe sizes shown on sheets P-1 and the riser diagrams on sheet P-2. All connected demands should be included in the water calculations.
12/05/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/12/2006 GBONILL1 FIRE REVIEW Needs Review
12/12/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
12/12/2006 GBONILL1 WWM REVIEW Needs Review
12/12/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review