Permit Number: T06CM06086
Parcel: 10703141D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM06086
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2006 STEVE SHIELDS ZONING REVIEW Approved
11/28/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
11/30/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The existing 1" water line and 1" water meter service the entire building. Reevaluate the sizes of these components.
2. Show the location of the pressure reducer for the building.
3. 9. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
11/30/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/30/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) FOR SEPERATED USE CLARIFY ADJACENT TENANTS AND REQUIRED FIRE SEPERATION ON EACH SIDE (EAST AND WEST).
2) VERIFY LAVATORY WILL NOT ENCROACH ON CLEAR FLOOR SPACE OF WATER CLOSET. FLOOR PLAN APPEARS TO HAVE LAV 1/2 INSIDE CLEAR FLOOR SPACE.
3) IF OFFICE SPACE EXCEEDS 10% INCIDENTAL USE ALLOWANCE THEN FIRE SEPERATION IS REQUIRED. PLEASE JUSTIFY NON-SEPERATED USE.
11/30/2006 ROBERT SHERRY WATER REVIEW Approved
11/30/2006 DAVE MANN FIRE REVIEW Approved
12/01/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
12/07/2006 DROBEY1 WWM REVIEW Completed
12/07/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/07/2006 DELMA ROBEY APPROVAL SHELF Completed
12/07/2006 DELMA ROBEY OUT TO CUSTOMER Completed
12/07/2006 DELMA ROBEY REJECT SHELF Completed