Permit Number: T06CM06085
Parcel: 10703141D

Review Status: Active

Review Details: COMMERCIAL TI

Permit Number - T06CM06085
Review Name: COMMERCIAL TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2006 STEVE SHIELDS ZONING REVIEW Approved
11/28/2006 ANY WWM REVIEW Active
11/28/2006 ANY ELECTRICAL-COMMERCIAL REVIEW Active
11/28/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
11/28/2006 ANY BUILDING-COMMERCIAL REVIEW Active
11/28/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active
11/30/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/30/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The existing 1" water line and 1" water meter service the entire building. Reevaluate the sizes of these components.
2. Show the location of the pressure reducer for the building.
3. 9. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
11/30/2006 ROBERT SHERRY WATER REVIEW Approved
11/30/2006 DAVE MANN FIRE REVIEW Approved