Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL TI
Permit Number - T06CM06085
Review Name: COMMERCIAL TI
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/28/2006 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 11/28/2006 | ANY | WWM | REVIEW | Active | |
| 11/28/2006 | ANY | ELECTRICAL-COMMERCIAL | REVIEW | Active | |
| 11/28/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 11/28/2006 | ANY | BUILDING-COMMERCIAL | REVIEW | Active | |
| 11/28/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Active | |
| 11/30/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/30/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The existing 1" water line and 1" water meter service the entire building. Reevaluate the sizes of these components. 2. Show the location of the pressure reducer for the building. 3. 9. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003. |
| 11/30/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/30/2006 | DAVE MANN | FIRE | REVIEW | Approved |