Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/28/2006 | DROBEY1 | ZONING | REVIEW | Completed | |
11/28/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. Please complete load calculations on panel schedule. 2. Please document source for AFC of 55,800A. 3. Note that 0.39 * 29.016 = 11,380A, not 8976. Please check fault calculations. 4. Please account for lumen multiplier of 0.2 in Outdoor Lighting Code Compliance calculations. |
11/28/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
11/28/2006 | JWILLIA5 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
11/28/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |