Permit Number: T06CM06082
Parcel: 10511040E

Address:
4280 N ORACLE RD

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - COMM

Permit Number - T06CM06082
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2006 DROBEY1 ZONING REVIEW Completed
11/28/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied 1. Please complete load calculations on panel schedule.
2. Please document source for AFC of 55,800A.
3. Note that 0.39 * 29.016 = 11,380A, not 8976. Please check fault calculations.
4. Please account for lumen multiplier of 0.2 in Outdoor Lighting Code Compliance calculations.
11/28/2006 DAVE MANN FIRE REVIEW Approved
11/28/2006 JWILLIA5 BUILDING-COMMERCIAL REVIEW Needs Review
11/28/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review