Permit Number - T06CM06078
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2007 SUZANNE BOHNET ENGINEERING REVIEW Denied Please submit a Floodplain Use Permit application. Include with the submittal current market value of the structure and a contractor's estimate of materials, supplies and labor for the proposed addition.
12/08/2006 GERRY KOZIOL WWM REVIEW Approved
12/15/2006 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity # T06CM06078

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

As of 9-02-04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the 2003 UPC with amendments. All plans should reference these codes. See this site for all adopted amendments: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

FOUNDATION PLANS:

1. Epoxy connections require special inspections. If used (detail 4/A.2), a special inspection request must be included with the permit application.

PLUMBING PLANS:

1. The City of Tucson has adopted the 2003 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). The plans should reference this code, or appeal to the Building Official for IRC design approval. All code references to the 1994 Code should be changed to 2003 (4 places) sheet P.1.
2. The pipe size shown on the Fixture Connection Schedule for the water heater (1 ΒΌ") is not as shown on the plan (1").

MECHANICAL PLANS:

1. Show dryer vent size and location, M1501.
2. Show bathroom exhaust fan rating (minimum 50 CFM) R303.3 and M1506.

ELECTRICAL PLANS:

1. Provide equipment rated for 22,000 AIC short circuit protection, 2006 Edition of Electric Service Requirements TEP SR-510.

OUTDOOR LIGHTING CODE

1. Show compliance with City of Tucson Outdoor Lighting Code; the total property lighting limit for area E3 is 55,000 lumens per acre and the unshielded limit for area E3 is 12,000 lumens per acre. Include all exterior fixtures on the property in the calculations. Show the exterior fixture wattage for determining lighting limits. Review guidance: www.ci.tucson.az.us/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf
2. Incandescent lamp cut-sheets may also be provided showing average lumen ratings, or the values of 60 watts = 850 lumens, 100 watts = 1700 lumens and 150 watts = 2850 lumens may be assumed. Select values for the maximum fixture rating. Show compliance for both total lumen output and the unshielded component fixture types.
3. Full cut-off fixtures have no emittance above the nadir (fixtures are completely opaque above and to the lowest point of the lamp). Fixtures may be exempt from the total lumen budget if both of the full cut-off FCO style and located under overhangs, OLC 5.1.2. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style).

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Clarify the inconsistency between the Energy Compliance Chart on sheet SP.1 showing a minimum of R-30 for ceilings and the Typical Roof Design notation on sheet A.3 showing R-22.
2. Tucson is in climate zone 4B, 2100 HDD, IRC chapter 11, local amendment. The simplified prescribed energy values for glazing U=0.65, ceiling R=19 and walls R=13 complies with 2003 IECC energy requirements if glazing does not exceed 12% of exterior wall area, or glazing U=0.65, ceiling R=30 and walls R=13 if glazing does not exceed 15% of exterior wall area. Show the window to wall calculation and energy values, or provide energy calculations per the 2003 IECC for compliance validations. Select the climate zone 4B, Pima County < 4000 ft, 2100 HDD if using REScheck. http://www.energycodes.gov/rescheck/ The solar heat gain coefficient SHGC should have a minimum value of 0.40.
3. Provide a note stating: A special insulation inspection or an insulation certificate is required before final inspection, N1101.3.1.

If you have any questions, please contact your assigned plans examiner Ken Van Karsen at 791-5550, extension 1112.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2007 FSANCHE1 OUT TO CUSTOMER Completed