Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM06072
Parcel: 14042002A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM06072
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
01/04/2007 GBONILL1 ENGINEERING REVIEW Needs Review
01/04/2007 GBONILL1 FIRE REVIEW Needs Review
01/04/2007 GBONILL1 ZONING REVIEW Needs Review
11/27/2006 JWILLIA5 ELECTRICAL-COMMERCIAL REVIEW Approved
11/29/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) YOU APPEAR TO BE MAKING TWO OCCUPANCIES OUT OF 1. THIS REQUIRES 2 PERMITS.
2) PLEASE SHOW ENTIRE BUILDING AREA AS ACTUAL AREA IN CODE ANALYSIS, NOT EACH OCCUPANCY. JUSTIFY NON-SEPERATED USE.
3) IBC 3409.5.1 YOU MAY NOT REDUCE THE ACCESSIBILITY OF AREA MARKED "LEASE SPACE" ON PLANS. BY SEPERATING THE OCCUPANCIES YOU APPEAR TO HAVE TAKEN AWAY ACCESS TO THE ACCESSIBLE RESTROOMS.
4) YOU NEED TO SPECIFY SOME TYPE OF OCCUPANCY FOR "LEASE SPACE".
11/30/2006 RSHERRY1 WWM REVIEW Passed
11/30/2006 ROBERT SHERRY WATER REVIEW Approved
11/30/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/26/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The drawing indicates that the existing 5-ton RTU has been relocated. Provide installation details and structural calculations to show that the new location has adequate support. Reference Section 302.1, IMC 2003.
2. Show the size, routing, and termination of the relocated condensate drains. Reference Section 307.2, IMC 2003 and Section 807.2, UPC 2003.
3. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.