Permit Number: T06CM06047
Parcel: 113010500

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T06CM06047
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2007 DAVE MANN FIRE REVIEW Denied On site fire hydrant required per C.O.T. amendments to the 2003 IFC (Section 508). Fire sprinklers will be accepted as an alternative.
02/16/2007 CRAIG GROSS ZONING REVIEW Denied 1. more detailed landscape plan required. show compliance with 3.7.2.3.A.1. information on plan is currently insufficient to provide for inspections.

2. all landscape areas are to be irrigated with a permanent irrigation system

3. continuous pedestrian access required for new building and parking (see attached plan)

4. correct setbacks for side and rear yard per section 3.5.4.9.B.1. (minimum 20 feet) sheet C-1 notes

5. please list any specific conditions of approval for original Board of Adjustment case C10-92-26.

6. provide signage at new driveway "No Right Turns"

7. is bicycle parking new or existing? Please label items as "new" or "existing"

8. are public sidewalks existing or proposed on Mountain Avenue and Duke Drive? If curbing exists then sidewalks are required.
02/23/2007 CRAIG GROSS NPPO REVIEW Approved NPPO Exception approved
02/23/2007 CRAIG GROSS LANDSCAPE REVIEW Denied see zoning comments
02/23/2007 CRAIG GROSS ZONING HC SITE REVIEW Denied see zoning comments
02/23/2007 SUZANNE BOHNET ENGINEERING REVIEW Denied Previous comments have been satisfactorily addressed.

A floodplain use permit is necessary.