Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM06041
Parcel: 126020020

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM06041
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2007 FSANCHE1 BUILDING-COMMERCIAL REVIEW Needs Review
01/25/2007 FSANCHE1 WWM REVIEW Needs Review
01/25/2007 FSANCHE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
01/25/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
11/24/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
11/24/2006 HEATHER THRALL ZONING REVIEW Approved
11/27/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/27/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the design of the trap arms for the foot spas so that there is no more than one trap on a trap arm. Reference Section 1001.1, UPC 2003.
2. Confirm the size of the water supply piping for the foot spas and the existing lavatory.
11/27/2006 ROBERT SHERRY WATER REVIEW Approved
11/27/2006 DAVE MANN FIRE REVIEW Approved