Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM06040
Parcel: 12709011M

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM06040
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/24/2006 STEVE SHIELDS ZONING REVIEW Approved
11/24/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
11/27/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM06040 11/27/06

1. Coordinate with Sheet A1 for new lighting fixtures.
2. Demonstrate that no phase of Panel 4P is overloaded.
3. Load on Ckt 7 appears to be 1260, not 540.
4. Load on Ckt 11 appears to be 720, not 540.
5. New receptacles would total more than the 580VA indicated on the panel schedule load calculations.
6. Account for largest motor load on panel schedule load calculations.
11/27/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Pumped condensate may not be directly connected to the plumbing system. Reference Sections 805.0 and 807.1, UPC 2003.
11/27/2006 DAVE MANN FIRE REVIEW Approved
11/27/2006 ROBERT SHERRY WATER REVIEW Approved
11/27/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/29/2006 GERRY KOZIOL WWM REVIEW Passed
11/29/2006 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review NEEDS REVIEW. OK TO SUBMIT.
11/29/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review