Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM06040
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/24/2006 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
11/24/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
11/27/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM06040 11/27/06 1. Coordinate with Sheet A1 for new lighting fixtures. 2. Demonstrate that no phase of Panel 4P is overloaded. 3. Load on Ckt 7 appears to be 1260, not 540. 4. Load on Ckt 11 appears to be 720, not 540. 5. New receptacles would total more than the 580VA indicated on the panel schedule load calculations. 6. Account for largest motor load on panel schedule load calculations. |
11/27/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Pumped condensate may not be directly connected to the plumbing system. Reference Sections 805.0 and 807.1, UPC 2003. |
11/27/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
11/27/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/27/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
11/29/2006 | GERRY KOZIOL | WWM | REVIEW | Passed | |
11/29/2006 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | NEEDS REVIEW. OK TO SUBMIT. |
11/29/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |