Permit Number: T06CM06039
Parcel: Unknown

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T06CM06039
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2007 GERRY KOZIOL WWM REVIEW Denied NEEDS WW / IWC / TOM TOMCHAK REVIEW OR SAND / OIL INTERCEPTOR 579-5771 - 5025 W INA RD
02/12/2007 ROBERT SHERRY WATER REVIEW Denied 1. Revise the site utility plan to show the location of the reduced pressure backflow assembly. Specify the reduced pressure backflow assembly being installed. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
2. Provide a letter from Tucson Water confirming that the use of a 1-1/2" water meter will be allowed for this project (174 fixture units, 85 GPM demand)
02/12/2007 DAVE MANN FIRE REVIEW Approved
02/20/2007 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed impact fees do apply, no development/site plan approved within deadline
western district
38,550 sf $38,550
02/23/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Million Air
T06CM06039
Building Plan (1st Review)

TRANSMITTAL DATE: February 23, 2007

Comments:
1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan at this time.

2. Detectable warnings (truncated domes) are required at all curb access ramps. ICC/ANSI A117.1-2003 Sec. 406.13. There are no detectable warning devices shown at the handicapped access aisle or the existing sidewalk apron.

1. The handicapped sign does not meet the requirements, see attached detail.

2. Zoning will re-review the building plan on the next submittal to ensure that all comments were addressed.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 791-5608 ext. 1180.

C:\planning\grading\t06cm06039.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised building plan and additional requested documents

Final Status

Task End Date Reviewer's Name Type of Review Description
03/01/2007 FSANCHE1 OUT TO CUSTOMER Completed
03/01/2007 SUE REEVES REJECT SHELF Completed