Permit Number: T06CM06037
Parcel: 119045050

Address:
3609 S 9TH AV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T06CM06037
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2007 DANIEL RUSCH BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity # T06CM06037



Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All dimensions and notes shall be consistent on each plan or elevation.

FLOOR PLANS:

1. Show compliance with R310 providing egress from bedrooms to meet the following minimum specifications.
Maximum sill height of 44".
Minimum net clear opening area of 5.7SF.
Minimum net clear opening dimension of 24" height and 20" width, and correct your note that states all openings are maximum 20" wide by 24" high.
2. Show under-floor space ventilation. Openings shall be not less than 1 SF for each 150 SF of area, R408.2. Show the location of a minimum 18"X24" access to under floor space that exceeds 30SF, R408.3. Show insulation values.
3. Floor plan note #1indicates doors on plan not trusses.
4. Note #2 is not shown anywhere on plan.
5. Note #4 refers to framing plan 3/2. I didn't locate 3/2.
6. Note #9 refers to SC rood to remain as is. Please explain.



STRUCTURAL PLANS:

1. Why do you provide complete roof framing plans? Are there any changes to building that would require this information to be pertinent?
2. What are you referring to on roof framing plan with Note #3

SECTIONS - DETAILS - MISC. NOTES:

1. On standard detail sheets, cross out all details that do not apply or are not being used.
2. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c framing, IRC table R702.3.5 footnote d. Please correct your note.

MECHANICAL PLANS:

1. Provide an equipment specification list including the heat pump. M1302.1.
2. Show the kitchen exhaust fan minimum 100-CFM rating, M1506.

ELECTRICAL PLANS:

1. Load calculations should indicate 3 VA for general lighting and convenience outlets. Calculations should also indicate water heater and A/C @100% of nameplate rating. Table E3502.2
2. Provide equipment rated for 22,000 AIC short circuit protection, 2006 Edition of Electric Service Requirements TEP SR-510.
3. Riser diagram indicates 400-amp service panel although electrical plan shows upgrade to 150-amp panel. Please clarify.
3. Receptacle outlets shall be provided at each kitchen counter space wider than 12", and shall be installed so that no point along the wall line is more than 24" from a receptacle outlet, E3801.4.1.
4. Range circuit wire under-sized.
5. Please clearly denote scope of work. Rewire, new circuits, etc.

OUTDOOR LIGHTING CODE

1. The City of Tucson Outdoor Lighting Code requires compliance for both total lumen output (E3: 55,000 lumens per acre) and the unshielded component (E3: 12,000 lumens per acre). Your calculations used wrong area (.16 acre), and total lumens not unshielded lumens.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Please indicate method of compliance with codes and stated insulation values.

If you have any questions, please contact your assigned plans examiner Daniel
Rusch at 791-5550, extension 1113