Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM06022
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/22/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) CLARIFY AND JUSTIFY INSTALLATION AND LOADS OF NEW HOOD EQUIPMENT. IT APPEARS STRUCTURAL CALCULATIONS WILL NEED TO BE PROVIDED TO JUSTIFY EXISTING STRUCTURE CAN CARRY THE NEW LOADS. 2) DRAWINGS SUBMITTED SHALL BE STAMPED AND SIGNED BY ARCHITECT. REVIEWED ONLY NOTATION IS NOT ACCEPTABLE. |
| 11/22/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide physical data for the hood (e.g. weight, materials, support connections, grease filters etc.). 2. Provide electrical and operating data for the exhaust fans. 3. Show how the hood is supported from the structure. 4. Provide clearance from the combustible supports or provide listed fire-wrap insulation to be installed around the hood. . Reference Section 506.3.10 (1), IMC 2003. 5. Provide information to show that the make up air for the kitchen hood complies with Section 508.1.1, IMC 2003. 6. Provide the operating characteristics of the make up air system. Show that the system provides adequate air flow. |
| 11/22/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM06022 11/22/06 Provide electrical plans for any equipment which uses electrical power. |
| 11/24/2006 | DROBEY1 | FIRE | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/24/2006 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 11/24/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 11/24/2006 | DELMA ROBEY | REJECT SHELF | Completed |