Permit Number: T06CM06022
Parcel: 131060250

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM06022
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/22/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) CLARIFY AND JUSTIFY INSTALLATION AND LOADS OF NEW HOOD EQUIPMENT. IT APPEARS STRUCTURAL CALCULATIONS WILL NEED TO BE PROVIDED TO JUSTIFY EXISTING STRUCTURE CAN CARRY THE NEW LOADS.
2) DRAWINGS SUBMITTED SHALL BE STAMPED AND SIGNED BY ARCHITECT. REVIEWED ONLY NOTATION IS NOT ACCEPTABLE.
11/22/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide physical data for the hood (e.g. weight, materials, support connections, grease filters etc.).
2. Provide electrical and operating data for the exhaust fans.
3. Show how the hood is supported from the structure.
4. Provide clearance from the combustible supports or provide listed fire-wrap insulation to be installed around the hood. . Reference Section 506.3.10 (1), IMC 2003.
5. Provide information to show that the make up air for the kitchen hood complies with Section 508.1.1, IMC 2003.
6. Provide the operating characteristics of the make up air system. Show that the system provides adequate air flow.
11/22/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM06022 11/22/06

Provide electrical plans for any equipment which uses electrical power.
11/24/2006 DROBEY1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/24/2006 DELMA ROBEY APPROVAL SHELF Completed
11/24/2006 DELMA ROBEY OUT TO CUSTOMER Completed
11/24/2006 DELMA ROBEY REJECT SHELF Completed