Permit Number: T06CM06005
Parcel: 13316020R

Address:
6586 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM06005
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/08/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/08/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM06005 12/08/06

1. It appears that "B-2" on the Electrical Lighting Plan is intended to read "B-4."
2. Panel B Phase A appears to be overloaded when the full 4776 VA for HP-2 is taken into account. This would account for 25% of the largest motor. NEC 430.24 requires that conductors which supply one or more motors, and other loads, shall have an ampacity not less than 125% of of the full load current rating of the largest motor plus the full load current ratings of all the other loads. By that criteria this conductor would be overloaded. Willing to discuss. 791.5550 x1106.
12/08/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/11/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/11/2006 DROBEY1 WWM REVIEW Needs Review