Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM06005
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/08/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/08/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM06005 12/08/06 1. It appears that "B-2" on the Electrical Lighting Plan is intended to read "B-4." 2. Panel B Phase A appears to be overloaded when the full 4776 VA for HP-2 is taken into account. This would account for 25% of the largest motor. NEC 430.24 requires that conductors which supply one or more motors, and other loads, shall have an ampacity not less than 125% of of the full load current rating of the largest motor plus the full load current ratings of all the other loads. By that criteria this conductor would be overloaded. Willing to discuss. 791.5550 x1106. |
| 12/08/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/11/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 12/11/2006 | DROBEY1 | WWM | REVIEW | Needs Review |