Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM06005
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/21/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 11/21/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide structural calculations to show that the new heat pump can be adequately supported on the roof. |
| 11/21/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM06005 11/21/06 1. Account for electrical load on panel schedule for Lighting on B-16. 2. Panel B Phase A appears to be overloaded when the full 4776 VA for HP-2 is taken into account. This would account for 25% of the largest motor. |
| 11/21/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/21/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/21/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 11/21/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide upper terminal cleanout for the 3" building drain. |
| 11/21/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/08/2006 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 12/08/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |