11/21/2006 HEATHER THRALL ZONING REVIEW Approved
11/21/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide structural calculations to show that the new heat pump can be adequately supported on the roof.
11/21/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM06005 11/21/06

1. Account for electrical load on panel schedule for Lighting on B-16.
2. Panel B Phase A appears to be overloaded when the full 4776 VA for HP-2 is taken into account. This would account for 25% of the largest motor.
11/21/2006 ROBERT SHERRY WATER REVIEW Approved
11/21/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
11/21/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
11/21/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide upper terminal cleanout for the 3" building drain.
11/21/2006 DAVE MANN FIRE REVIEW Approved
12/08/2006 GBONILL1 WWM REVIEW Needs Review
12/08/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review