Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05973
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/21/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 11/21/2006 | BETSY COTTLE | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/24/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. The floor shall slope towards the floor drain in a toilet room (see note in Detail 3/M5). Reference Section 412.2.1, UPC 2003. 3. Provide information to show that the hose connection vacuum breaker for the roof hatch (Detail 6/M2 and keynote 15.405) is listed for use when mounted upside down. Reference Section 310.4, UPC 2003. 4. If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 btu per inch/h °F on the first 8 feet of supply and discharge piping. Reference Sections 804.4 and 804.5, IECC 2003. 5. All storage-type water heaters require a listed expansion tank. Please show expansion tanks on plans. Reference Section 608.3, UPC 2003 with local amendments. 6. Indirect waste receptors shall be installed in readily accessible locations, not inside of a closet or cupboard (see FD-1, 1/MPL1), and shall be designed to prevent splashing or flooding. Reference Section 804.1, UPC 2003. 7. Revise the size of the vent for FD-1, as shown in detail 2/MPL1, to comply with the size requirements shown in Table 7-5, UPC 2003. Show the sizes of the unlabeled vents. 8. Provide a cleanout for the sink in the photo lab. Reference Section 707.4 (1), UPC 2003. |
| 11/24/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/24/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Provide the refrigeration schedule and refrigerant piping drawing noted on sheet R1 along with the refrigeration capacities for the new equipment. Show that the equipment meets the requirements of Section 1102.1, IMC 2003. |
| 12/14/2006 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) CLARIFY ADDITIONAL LOADS AND PROVIDE STRUCTURAL CALCULATIONS FOR COILING DOOR AT PHARMACY. REF: PP PH3. 2) REFERENCE NOTE ON PP A3 FOR FLAT FLOOR. 2003 UPC REQUIRES A SLOPE OF 1/8" PER FOOT TO FLOOR DRAINS IN BATHROOMS. |
| 12/14/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. Reference Sheet E1.1 Detail 1. 2. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. Reference Sheet E1.1 Detail 2. 3. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. Reference Sheet E2.4 Detail 4. 4. On Sheet E1.1, Keynote 16.W24 appears to contradict the panel/circuit designation HC-34. 5. On Sheet E2, Detail 1, the note regarding circuit loading appears to contradict the loads indicated on Panel L2D. 6. Address disconnecting means for coolers on Sheet E2, Detail 1. Reference NEC 422 Part III. 7. Ckt L1F-1 powers busway on Sheet E2, Detail 3. This Ckt is part of a 3-P breaker on the Panel Schedule. Please clarify. 8. Refrigeration Electrical Equipment Schedule on Sheet RE1, #MT-R3A provides a 30A CB for a 31.67A load. Please clarify. 9. Equipment #MT-R3A a 31.67A load, would have 3.80 KVA, not 2.78. Reference Panel L2R Sheet E4.1. 10. For the Busway BL1A, and L1F and L2D panel schedule load calculations, please reference the exact demand factor used and Code Section in Article 220. Note that 220.13 demand factors may only be applied to receptacle loads computed at not more than 180 VA per outlet. 11. Provide the feeder size for Panel L1U. Reference Sheet E4.1 Panel Schedule L1F. 12. Phase B of Panel HC appears to be overloaded, considering continuous loading. Reference Sheet E4.1. 13. Did not see location of Transformer TPL on the plans. 14. If Transformer TG is existing, please indicate on Riser Diagram. Otherwise, add to Transformer Schedule. 15. The #4 GR on the secondary to TD is properly sized at #2, not #4. Reference NEC Table 250.66. 16. For the Panel HB panel schedule load calculations, please reference the exact demand factor used and Code Section in Article 220. Note that 220.13 demand factors may only be applied to receptacle loads computed at not more than 180 VA per outlet. Additionally, it appears that loads on CKT 1,3,5, are 25.41, 24.55, and 12.84 VA, not 24.16, 24.05, and 11.59 VA, respectively. It appears that loads on CKT 49,51,53 are 49.45, 50.98, and 48.94 VA, not 35.69, 36.49, and 38.56 VA, respectively. It appears that CKT 43 load is 8.98 VA, not 7.44. Panel HB, its feeder and circuit rating appear to be overloaded at 662.30 A. 17. Provide load calculations for Switchboard MSWB. Connected Loads Table shows a 10 HP New Motor, but N/A in other columns. Demand factors for continuous load shown as 1.00. It may add clarity to simply add new loads to existing peak demand after such demand has been adjusted according to the requirements of NEC 220.35 and after power factor has been taken into consideration. 18. MSWB, with AFC of 20,647, is rated for only 14,000 AIC. |
| 12/21/2006 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/30/2007 | FSANCHE1 | OUT TO CUSTOMER | Completed |
| 01/30/2007 | SUE REEVES | REJECT SHELF | Completed |