Permit Number: T06CM05967
Parcel: 113111550

Address:
1816 E SENECA ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T06CM05967
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/24/2006 GERRY KOZIOL WWM REVIEW Denied 1:SFR REMODEL- RECOUNTED ALL WASTEWATER PLUMBING FIXTURES, NEEDS 8TH FLOOR CREDIT EVALUATION (PERMIT #PT02S04588 NOT ISSUED).
2:NEEDS WASTEWATER DESIGN REVIEW OF LIFT STATION BY HOWARD WOOLCROFT- 617-8207- 100 N STONE AV.
3:DOES NOT INCLUDE REAR DETACHED GARAGE/STORAGE/PORCH BUILDING PERMITTED WITH #PT97S00050
12/17/2006 LINHART PETERSEN POERS ASSOC. 2ND PARTY REVIEW REVIEW Denied December 13, 2006 CITY OF TUCSON - FIRST CHECK
Tucson Appl. No. T06CM05967
Bureau Veritas Project No. 01006-161105
Mr. Thomas Hayes
10957 N. First Ave
Tucson, Arizona 85737



Re: Plan Review: Burrell Addition/Remodel
Address: 1816 E. Seneca St

Dear Mr. Hayes:

Bureau Veritas North America has completed a review of the following documents on behalf of the City of Tucson:

Plans: Two (2) copies of plans (13 sheets, 1 through 13) Architectural dated August 16, 2006 by Marc Soloway – Structural dated July 28, 2006 by John E. Grenier.

Structural Calculations: One (1) copy of calculations dated July 28, 2006 by John E. Grenier.



These documents were reviewed only for their conformance to the provisions of the 2003 International Building Codes (i.e., State of Arizona and Tucson amended 2003 IRC, 2003 IMC, 2002 NEC and 2003 IPC).

Please submit an itemized response letter and required number of complete and revised documents with all revisions clouded.



Sincerely,

BUREAU VERITAS NORTH AMERICA



Randy McCoy
ICC Plans Examiner








RM:pc S:\Tucson\01006-1610105pc1.doc
Enclosures





Burrell Addition/Remodel City of Tucson - First Check
1816 E. Seneca Street Bureau Veritas Project No.:01006-161105
December 13, 2006 Page


A. The following plan review comments are based on the City of Tucson Building Regulations and referred to the 2003 International Residential Code.

B. Please respond in writing to each comment by marking the attached comment list or creating a response letter. Indicate which detail, specification, or calculation shows the requested information. Your complete and clear responses will expedite the re-check and hopefully, approval of this project. Thank you for your assistance.

C. These plan review comments are based on building code items only. If site-related comments are applicable to this project, they will be generated by others (e.g., County Engineering, Public Works, Health, etc.).

STAIR REQUIREMENTS:

Please provide details showing stair construction, connection details and stringer sizes.

The minimum headroom in all parts of the stairway shall be not less than 6 feet 8 inches measured vertically from the slope plane adjoining the tread nosing or from the floor surface of the landing platform. IRC Section R314.3.


FOUNDATION PLAN COMMENTS:

Note and specify termite protection. IRC Section R324.


MECHANICAL COMMENTS:

Show condensate line and secondary condensate line. IRC Section M1411.3 and M1411.3.1.



If you have any questions regarding the above comments, please contact Randy McCoy at (520) 820-1980 between 8:00 A.M. to 5:00 P.M., M-F.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/21/2006 FSANCHE1 OUT TO CUSTOMER Completed