Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM05951
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/04/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. On Ckt 6, 1/8" scale, there are 25 LF of track lighting. (25) (75) = 1875 (1.25) = 2344, not 1875. Please clarify. 2. On Ckt 14, 1/8" scale, there are 30 LF of track lighting. (30) (75) = 2250 (1.25) = 2813, not 1688. 3. Account for largest motor on panel load calculations. |
| 12/04/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Correct the water pressure calculations and resize the water pipes as required. |
| 12/04/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/05/2006 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 12/05/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 12/05/2006 | DROBEY1 | FIRE | REVIEW | Needs Review | |
| 12/05/2006 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/05/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |