Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied 1. On Ckt 6, 1/8" scale, there are 25 LF of track lighting. (25) (75) = 1875 (1.25) = 2344, not 1875. Please clarify.
2. On Ckt 14, 1/8" scale, there are 30 LF of track lighting. (30) (75) = 2250 (1.25) = 2813, not 1688.
3. Account for largest motor on panel load calculations.
12/04/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Correct the water pressure calculations and resize the water pipes as required.
12/04/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/05/2006 DROBEY1 WWM REVIEW Needs Review
12/05/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/05/2006 DROBEY1 FIRE REVIEW Needs Review
12/05/2006 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/05/2006 DELMA ROBEY OUT TO CUSTOMER Completed