Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM05949
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05949
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2006 JASON GREEN ENGINEERING REVIEW Approved
11/20/2006 TERRY STEVENS ZONING REVIEW Approved
11/21/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Provide details for the installation of the grease trap and the 3-compartment sink. Only the sanitizing compartment is to be indirectly wasted. The grease trap shall be directly wasted.
3. Clarify how the grease trap and the flow control device are to be vented.
4. Appliances (e.g. espresso machines, ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2003 require individual backflow prevention. Show how each appliance will be connected and list any backflow protection assemblies being used. Reference Sections 602.3, 603.0, and Table 6-2, UPC 2003.
11/21/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
11/21/2006 ROBERT SHERRY WATER REVIEW Approved
11/21/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide mechanical information for the new walk-in freezer.
11/21/2006 DAVE MANN FIRE REVIEW Approved
12/27/2006 FSANCHE1 BUILDING-COMMERCIAL REVIEW Needs Review 1) WHAT IS VALUATION?
2) PROVIDE LEGIBLE LOCATION PLAN SHOWING CLEAR AISLE WIDTHS FOR VERIFICATION OF SECTION 402.10(3) OF IBC.
3) VEIRFY COMPLIANCE WITH IBC SECTION 2902.6.1 FOR RESTROOM FACILITIES.
4) DETAIL COUNTER HEIGHTS FOR ACCESSIBILITY PER ANSI A117.1 SECTION 904.
12/27/2006 FSANCHE1 WWM REVIEW Needs Review
12/27/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/27/2006 FSANCHE1 OUT TO CUSTOMER Completed