Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM05925
Parcel: 10603035A

Address:
131 E MOHAVE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM05925
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2007 DAVE MANN FIRE REVIEW Approved
03/15/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Sunshine Child Care
131 E. Mohave
T06CM05925
Building Plan

TRANSMITTAL DATE: March 15, 2007

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan at this time.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please call Steve Shields,
(520) 791-5608 ext. 1180.

C:\planning\building\t06cm05925.doc


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved and stamped site plan and additional requested documents
03/19/2007 GERRY KOZIOL WWM REVIEW Denied 1:SHINE CHILD CARE- DAYCARE- SFR TO COMMERCIAL RECOUNTED ALL WASTEWATER PLUMBING FIXTURES- NEEDS 8TH FLOOR CREDIT EVALUATION.
2:NEEDS 8TH FLOOR REVIEW IF APPLICABLE OF EXSISTING CONNECTION OF 135 E MOHAVE RD (REAR PARCEL #2)-EXSISTING SFR & GUEST HOUSE- LOT LINE ADJUSTMENT
03/23/2007 SUZANNE BOHNET ENGINEERING REVIEW Denied Building plans will be approved once Site Plan is approved.
04/09/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Ventilation for restrooms in public spaces requires a minimum of 75 CFM of mechanical exhaust per water closet or urinal. Reference Table 403.3, IMC 2003.
04/09/2007 WILDAN 2ND PARTY REVIEW REVIEW Denied 201 N. Stone Avenue
Tucson, AZ 85701

RE: SUNSHINE CHILD DAYCARE STRUCTURAL– 2nd REVIEW
CITY OF TUCSON LOG NO. T06CM05925
WILLDAN PROJECT NO. 13881-6090

The second review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter third review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IBC, 1997 UAC, 2003 IMC, 2003 IECC, 2002 NEC, and the 2003 UPC. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Chris Kiel.

Also, please note that per paragraph V-C of the 3rd Party Agreement, third and subsequent reviews will be charged at the current hourly rate in addition to the base contract amount.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
E, I-4? 87? VB 2184 No? Yes
See general comment #1 for additional information.

Special Inspection is required for the following items:
N/A

The following items are acceptable for deferred submittals:
N/A

GENERAL COMMENTS:
Please provide exit signage per section 1011 of the 2003 IBC and egress illumination per section 1006 with emergency power per section 1006.3 of the 2003 IBC. If new lights are added that increase the total wattage for the building, please provide verification of compliance with section 805.5.2 of the 2003 IECC. COMMENT REMAINS: Please coordinate the removal of the wall between areas #4 and #5 between all of the plans sheets per section 106.1.1 of the 2003 IBC.


ARCHITECTURAL COMMENTS:
Sheet A1.0
Please provide additional information regarding the door hardware in order to verify compliance with sections 1008.1.8.3 and 1013.2 of the 2003 IBC. COMMENT REMAINS: The current submittal still does not provide any information regarding the door hardware in order to verify compliance with sections 1008.1.8.3 of the 2003 IBC.

Please provide accessible exits in accordance with sections 1007.1 and 1014.2 of the 2003 IBC (i.e. accessible route, landings, maneuvering clearances, exit arrangement, etc.). COMMENT REMAINS: Please revise the rear exit ramp bottom landing to match the width of the ramp per section 1010.6.2 of the 2003 IBC. In addition, please specify the height of the handrail extension return in order to verify compliance with section 1003.3.3 of the 2003 IBC. Finally, provide information regarding the gate hardware in order to verify compliance with section 1008.1.8.3 of the 2003 IBC.

Please provide additional information regarding the rear exits in order to verify compliance with chapter 10 of the 2003 IBC and ANSI 117.1-2003. COMMENT REMAINS: The current submittal still does not provide any information regarding the other rear exits in order to verify compliance with chapter 10 of the 2003 IBC.

Sheet C1.0
Please provide additional information regarding the ramps in order to verify compliance with section 405 of ANSI 117.1-2003 and section 1010 of the 2003 IBC (i.e. rise, run, landings, handrail, edge protection, etc.). COMMENT REMAINS: See the previous comment regarding the rear ramp.

Please provide additional information regarding the rear exits and associated sidewalk in order to verify compliance with chapter 10 of the 2003 IBC regarding egress to the public way and ANSI 117.1-2003 regarding accessibility. Please provide additional information regarding the rear cmu wall in order to verify compliance with the exit discharge requirements of section 1023.6 of the 2003 IBC. COMMENT REMAINS: See the previous comment regarding rear exits and the gate hardware.

Sheet D1.0
Please provide vertical grab bars at the water closets per section 604.5.1 of ANSI 117.1-2003. In addition, please provide additional information regarding placement of the rear grab bar in order to verify compliance with section 604.5.2 of ANSI 117.1-2003. COMMENT REMAINS: The current submittal still doesn’t specify the placement of the rear grab bar in order to verify compliance with section 604.5.2 of ANSI 117.1-2003.

Please provide pipe protection at the lavatory in accordance with section 606.6 of ANSI 117.1-2003. COMMENT REMAINS: The current submittal still doesn’t specify the required pipe protection at the lavatory per section 606.6 of ANSI 117.1-2003.

STRUCTURAL COMMENTS:
Reviewed and accepted.

PLUMBING COMMENTS:
Reviewed by the City of Tucson.


MECHANICAL COMMENTS:
Reviewed by the City of Tucson.

ELECTRICAL COMMENTS:
Reviewed by the City of Tucson.

ENERGY CODE COMMENTS:
Reviewed and accepted.

ACCESSIBILITY COMMENTS:
Please refer to the Architectural Comments for issues concerning accessibility.

Sincerely,

WILLDAN




Chris Kiel, C.B.O., M.C.P.
Building Official

CEK/tb
04/09/2007 ROBERT SHERRY WATER REVIEW Approved
04/09/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Second request. Provide the location and size of the reduced pressure backflow preventer assembly for the building. Reference Section 103.2.3, UPC 2003.
2. The revised site plan indicates that the building sewer extends to the north of the new building drain. If the extension of the existing building sewer is connected to a building on an adjacent lot, provide a recorded joint sewer use agreement. Reference Sections 103.2.3 and 312.0, UPC 2003.
3. Show the location of cleanouts in the building sewer, including the required cleanout for the junction of the new building drain and the building sewer. Reference Section 719.0, UPC 2003.
4. Show that the building has adequate vents, per Section 904.1, UPC 2003.
5. Show how the new water piping relates to the existing water supply for the kitchen sink and the dishwasher. Reference Section 101.5.1, UPC 2003.
6. According to Tucson Water, the water pressure delivered to this address has a range of 66-73 psig, not 80 psig. Also, the specified water closet, P2, requires a minimum pressure of 20 psig, not 15 psig. Revise the water pressure calculations accordingly and include the pressure drop attributable to the backflow preventor for the building. Reference Section 610.0, UPC 2003.
7. Provide the manufacturer's specification sheets for water closet P2H and for the drinking fountain, P4, to demonstrate that they are accessible per ADA requirements. Reference Section 103.2.3, UPC 2003.
8. Show how the traps for the restroom floor drains are to be primed. Reference Section 1007.0, UPC 2003, as amended by the City of Tucson.
9. Show that the restroom floors are sloped to the floor drains. Reference Section 412.2, UPC 2003.
10. Second request. Provide a detail showing the size and termination of the vent for the relocated water heater. Reference Section 510.3.3, UPC 2003. Show that the location of the termination of the gas vent complies with Section 510.6.2.1, UPC 2003, especially with regard to being at least 8 feet from any vertical surface (e.g. a roof top appliance).

Final Status

Task End Date Reviewer's Name Type of Review Description
04/13/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
04/13/2007 SUE REEVES REJECT SHELF Completed