Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM05925
Parcel: 10603035A

Address:
131 E MOHAVE RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05925
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/27/2006 DAVE MANN FIRE REVIEW Denied Needs landings at doors. IFC 1008.1.5
Need fire sprinklers or legal exits to exterior from all activity areas per 2003 IFC, C.O.T. amendment to Section 903.2.2
Separate permit will be required for fire alarm system.
11/27/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide a Type I hood over the domestic range being used for commercial purposes. Reference Section 507.2.3, IMC 2003.
11/27/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide equipment data for the water heater. Reference Section 103.2.3, UPC 2003.
2. Provide site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference Section 103.2.3, UPC 2003.
3. Show how the new waste piping connects to the existing building drain and then to the building sewer line. Reference Section 103.2.3, UPC 2003.
4. Show how the new water piping relates to the existing water supply system and show that the additional connections do not cause the existing piping to be overloaded. Reference Section 101.5.1, UPC 2003.
5. Provide a natural gas schematic showing the loads and developed lengths of the piping. Reference Section 103.2.3, UPC 2003.
6. Provide floor drains in the restrooms. Reference Section 412.2, UPC 2003.
7. Show how the temperature of the hot water supply to the lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
8. Show that the net free area of the specified combustion air ducts meets the requirements of Section 507.4, UPC 2003. Reference Section 507.9, UPC 2003 as amended by the City of Tucson.
9. Provide a detail of the water heater installation, including the temperature-pressure relief, expansion tank, and valves. Reference Sections 103.2.3, 605.5, and 608.3 UPC 2003.
10. Provide a detail showing the size and termination of the vent for the relocated water heater. Reference Section 510.3.3, UPC 2003.
11. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length). Reference Section 707.4, UPC 2003.
11/27/2006 ROBERT SHERRY WATER REVIEW Denied Provide a reduced pressure backflow assembly for the water service. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
11/30/2006 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Sunshine Child Care
131 E. Mohave
T06CM05925
Building Plan

TRANSMITTAL DATE: November 30, 2006

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan at this time.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please call Steve Shields,
(520) 791-5608 ext. 1180.

C:\planning\building\t06cm05925.doc


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved and stamped site plan and additional requested documents
12/04/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
12/04/2006 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/18/2006 SUZANNE BOHNET ENGINEERING REVIEW Denied Building plans out for review with Wildan - cannot be approved until Site Plan is approved by all depts.
12/22/2006 WILDAN BUILDING-COMMERCIAL REVIEW Denied December 21, 2006

City of Tucson Development Services
201 N. Stone Avenue
Tucson, AZ 85701

RE: SUNSHINE CHILD DAYCARE STRUCTURAL– 1ST REVIEW
CITY OF TUCSON LOG NO. T06CM05925
WILLDAN PROJECT NO. 13881-6090

The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IBC, 1997 UAC, 2003 IMC, 2003 IECC, 2002 NEC codes with local modifications, and the 2003 UPC with State of Arizona Amendments. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Chris Kiel.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
E, I-4? 87? VB 2184 No? Yes
See general comment #1 for additional information.

Special Inspection is required for the following items:
N/A

The following items are acceptable for deferred submittals:
N/A

GENERAL COMMENTS:
Please provide additional information regarding the age of the children in the facility in order to verify the use of the property per chapter 3 of the 2003 IBC (E vs. I-4). If the facility is determined to be an I-4 occupancy, please revise the occupant load and provide a sprinkler system accordingly.

Please provide exit signage per section 1011 of the 2003 IBC and egress illumination per section 1006 with emergency power per section 1006.3 of the 2003 IBC. If new lights are added that increase the total wattage for the building, please provide verification of compliance with section 805.5.2 of the 2003 IECC.


ARCHITECTURAL COMMENTS:
Sheet A1.0
Please revise the ramp at the main entry to provide landings and the required maneuvering clearance per sections 405.7 and 404.2.3 of ANSI 117.1-2003.

Please provide additional information regarding the door hardware in order to verify compliance with sections 1008.1.8.3 and 1013.2 of the 2003 IBC.

Please provide accessible exits in accordance with sections 1007.1 and 1014.2 of the 2003 IBC (i.e. accessible route, landings, maneuvering clearances, exit arrangement, etc.).

Please provide additional information regarding the rear exits in order to verify compliance with chapter 10 of the 2003 IBC and ANSI 117.1-2003.

Sheet C1.0
Please provide additional information regarding the ramps in order to verify compliance with section 405 of ANSI 117.1-2003 and section 1010 of the 2003 IBC (i.e. rise, run, landings, handrail, edge protection, etc.).

Please provide additional information regarding the rear exits and associated sidewalk in order to verify compliance with chapter 10 of the 2003 IBC regarding egress to the public way and ANSI 117.1-2003 regarding accessibility. Please provide additional information regarding the rear cmu wall in order to verify compliance with the exit discharge requirements of section 1023.6 of the 2003 IBC.

Sheet D1.0
Please provide vertical grab bars at the water closets per section 604.5.1 of ANSI 117.1-2003. In addition, please provide additional information regarding placement of the rear grab bar in order to verify compliance with section 604.5.2 of ANSI 117.1-2003.

Please provide pipe protection at the lavatory in accordance with section 606.6 of ANSI 117.1-2003.

STRUCTURAL COMMENTS:
Reviewed and accepted.

PLUMBING COMMENTS:
Reviewed by the City of Tucson.

MECHANICAL COMMENTS:
Reviewed by the City of Tucson.

ELECTRICAL COMMENTS:
Reviewed by the City of Tucson.

ENERGY CODE COMMENTS:
Reviewed and accepted.

ACCESSIBILITY COMMENTS:
Please refer to the Architectural Comments for issues concerning accessibility.


Sincerely,

WILLDAN




Martin Haeberle, C.B.O.
Building Official

MAH/tb
12/27/2006 GERRY KOZIOL WWM REVIEW Denied 1:SHINE CHILD CARE- DAYCARE- SFR TO COMMERCIAL RECOUNTED ALL WASTEWATER PLUMBING FIXTURES- NEEDS 8TH FLOOR CREDIT EVALUATION.
2:NEEDS 8TH FLOOR REVIEW IF APPLICABLE OF EXSISTING CONNECTION OF 135 E MOHAVE RD (REAR PARCEL #2)-EXSISTING SFR & GUEST HOUSE- LOT LINE ADJUSTMENT

Final Status

Task End Date Reviewer's Name Type of Review Description
01/02/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
01/02/2007 SUE REEVES REJECT SHELF Completed