Permit Number: T06CM05909
Parcel: 128030110

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05909
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2006 TERRY STEVENS ZONING REVIEW Approved
11/15/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
11/24/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Correct the arithmetic for the water fixture units. Reevaluate the required size of the water service pipe.
2. Clarify the drainage for the foot spas. Gravity drains shall be directly wasted.
3. Justify the flat vent for the new water closet.
11/24/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/24/2006 MARTIN BROWN FIRE REVIEW Approved
11/24/2006 ROBERT SHERRY WATER REVIEW Approved
11/27/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM05909 11/27/06

1. Recirculation pump is cord connected. Reference Sheet P4.
2. Provide mounting height, luminaire cut sheets, and any other information necessary to determine compliance with NEC 680.43 (B).
3. Plans Examiner got 13810 VA on Phase A, not 11495.
4. Total current for Panel A exceeds its 100A capacity.
5. Panel schedule calls for 100A panel. One Line Diagram calls for 200A panel. Please clarify.
11/27/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Provide water fountain HIGH AND LOW PER PER 602.4
2) Provide exit accessibility for door of north restroom.
12/22/2006 CAGUILA1 WWM REVIEW Needs Review
12/22/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/22/2006 CINDY AGUILAR OUT TO CUSTOMER Completed