Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05897
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 01/05/2007 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 11/15/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 11/15/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 12/20/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/20/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 12/20/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE VALUATION FOR SCOPE OF WORK 2) IT APPEARS RESTROOMS ARE NOT FULLY ACCESSIBLE PER ANSI A117.1 2003. PLEASE CLARIFY / JUSTIFY. PER SECTION 3409.6 IBC 2003 CLARIFY 20% COST OF CONSTRUCTION SPENT TOWARDS ACCESSIBILITY. OR PROVIDE INFORMATION OFN DRAWING WHERE ACCESSIBLE RESTROOMS ARE LOCATED PER CODE. 3) PER NOTE 15 & 16 CLARIFY ACCESSIBILITY FOR BREAKROOM SINK PROVIDE ELEVATION OF CABINET CLARIFYING HEIGHT. 4) INTERIOR PARTITION TOP TRACK SHALL NOT BE ATTACHED TO THE "T" GRID. |
| 12/20/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/20/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/20/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved |