Permit Number: T06CM05873
Parcel: 140420440

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05873
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) THIS BUILDING CANNOT BE JUSTIFIED BY UNLIMITED SQ. FOOTAGE. THE EAST WALL IS TO CLOSE TO THE PROPERTY LINE.
11/15/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the mechanical system relates to the property line.
11/15/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM05873 11/15/06

See review comments for Ste 100, T06CM05872.

11/22/06
Demonstrate compliance with NEC 240.24 (B), 230.72 (C), and 230.92. If the "Service Riser" indicated on Sheet A2.0 includes the service disconnecting means, please state so on the plans. Regarding any other overcurrent devices, each occupant shall have ready access to all overcurrent devices supplying that occupancy. This needs to be clear on the plans.
11/15/2006 ROBERT SHERRY WATER REVIEW Denied Show the presence of a backflow preventor for the water service.
11/15/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show how the plumbing relates to the property line.
11/22/2006 GBONILL1 WWM REVIEW Denied
11/22/2006 GBONILL1 ZONING REVIEW Needs Review
11/22/2006 GBONILL1 ENGINEERING REVIEW Denied
11/22/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
11/22/2006 GBONILL1 FIRE REVIEW Needs Review