Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05873
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/15/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) THIS BUILDING CANNOT BE JUSTIFIED BY UNLIMITED SQ. FOOTAGE. THE EAST WALL IS TO CLOSE TO THE PROPERTY LINE. |
| 11/15/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how the mechanical system relates to the property line. |
| 11/15/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM05873 11/15/06 See review comments for Ste 100, T06CM05872. 11/22/06 Demonstrate compliance with NEC 240.24 (B), 230.72 (C), and 230.92. If the "Service Riser" indicated on Sheet A2.0 includes the service disconnecting means, please state so on the plans. Regarding any other overcurrent devices, each occupant shall have ready access to all overcurrent devices supplying that occupancy. This needs to be clear on the plans. |
| 11/15/2006 | ROBERT SHERRY | WATER | REVIEW | Denied | Show the presence of a backflow preventor for the water service. |
| 11/15/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show how the plumbing relates to the property line. |
| 11/22/2006 | GBONILL1 | WWM | REVIEW | Denied | |
| 11/22/2006 | GBONILL1 | ZONING | REVIEW | Needs Review | |
| 11/22/2006 | GBONILL1 | ENGINEERING | REVIEW | Denied | |
| 11/22/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 11/22/2006 | GBONILL1 | FIRE | REVIEW | Needs Review |