Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM05866
Parcel: 12801005H

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T06CM05866
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM05866 12/18/06

1. Water Heater is 2-2000W, 115/1/60 on Sheet P1. Electrical powers 3000W, 208V WH. Coordinate with Mechanical and clarify.
12/18/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/19/2006 CINDY AGUILAR APPROVAL SHELF Completed
12/19/2006 CINDY AGUILAR OUT TO CUSTOMER Completed