Permit Number: T06CM05853
Parcel: 119041280

Address:
344 W AJO WY

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05853
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
11/14/2006 STEVE SHIELDS ZONING REVIEW Approved
11/14/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the new areas are being ventilated, include the outside air calculations.
11/14/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
11/14/2006 ROBERT SHERRY WATER REVIEW Approved
11/14/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE SITE PLAN SHOWING BUILDING FOOT PRINT, PROPERTY LINES, AND PARKING. CLARIFY OCCUPANCIES OF BUILDING FOR SEPARATED / NON SEPARATED USE.
2) PROVIDE ACCURATE CODE ANALYSIS.
3)PROVIDE STRUCTURAL CALCULATION TO JUSTIFY NEW OPENINGS IN BEARING WALL.
4) CLARIFY LOCATION OF RESTROOMS JUSTIFYING OCCUPANT LOAD AND FIXTURE COUNT PROVIDED.
5)PER CHAPT 3409.6 20% COST OF CONSTRUCTION SPENT TOWARDS ACCESSIBILITY.
11/14/2006 RSHERRY1 WWM REVIEW Passed
11/14/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/14/2006 DAVE MANN FIRE REVIEW Approved
11/27/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/27/2006 FSANCHE1 OUT TO CUSTOMER Completed