Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM05816
Parcel: 14108534A

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T06CM05816
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2006 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/04/2006 DAVE MANN FIRE REVIEW Denied The sprinkler density in IFC Table 3404.3.6.3 exceeds the density on the plans.

TJI's and plywood are not allowed in type IIB construction, IBC 603.1.

Separate permits are required for the outdoor tank and sprinklers.

Door 104 should have panic hardware, IFC 1008.1.9.

Show locations of NFPA 704 placards.

The tank size may not be adequate for flow required by IFC Chapt. 27. 6205 gal ?
12/05/2006 GERRY KOZIOL WWM REVIEW Denied NEEDS IWC REVIEW-TOM TOMCHAK- 579-5771
12/05/2006 ROBERT SHERRY WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/11/2006 DELMA ROBEY OUT TO CUSTOMER Completed
12/11/2006 SUE REEVES REJECT SHELF Completed